No Load Behavior Prediction of Large Five-Legged Transformers Using Topological Transient Models

Authors

Sergey Zirka
Dnipro National University, Department of Physics and Technology
https://orcid.org/0000-0001-7607-1436
Dennis Albert
OMICRON electronics GmbH
https://orcid.org/0000-0001-8916-851X
Alexander Fröhlich
Graz University of Technology, Institute of Electrical Power Systems
https://orcid.org/0009-0009-2414-6956

Synopsis

The work proposes a method of reproducing the no-load losses and currents of large five-legged transformers with the use of their transient models. This aim is achieved by employing topological transformer models based on a dynamic hysteresis model (DHM) and taking into account equivalent transformer capacitances. It is proposed to reproduce initially the measured total losses by using DHM means, and then to determine an equivalent per phase capacitance value that provides a best possible coincidence of calculated and measured current waveforms.

Author Biographies

Sergey Zirka, Dnipro National University, Department of Physics and Technology

Dnipro, Ukraine. E-mail: zirka@email.dp.ua

Dennis Albert, OMICRON electronics GmbH

Klaus, Austria. E-mail: dennis.albert@omicronenergy.com

Alexander Fröhlich, Graz University of Technology, Institute of Electrical Power Systems

Graz, Austria. E-mail:  a.froehlich@tugraz.at

Downloads

Published

May 14, 2025

How to Cite

No Load Behavior Prediction of Large Five-Legged Transformers Using Topological Transient Models. (2025). In XXVIII. Symposium Electromagnetic Phenomena in Nonlinear Circuits (EPNC 2024): Conference Proceedings (pp. 241-246). University of Maribor Press. https://press.um.si/index.php/ump/catalog/book/963/chapter/487